Type
|
Specification
|
|
Wirings
|
1P2W, 1P3W, 3P3W, 3P4W
|
|
Input
|
Frequency
|
60Hz/50Hz
|
|
Voltage
|
PT
|
110V
|
|
GPT
|
190V
|
|
Current
|
CT
|
5A
|
|
ZCT
|
200/1.5mA
|
|
Control voltage
|
AC/DC 110V or DC 125V
|
|
Power consumption
|
Max. 30W
|
|
Burden
|
PT
|
Max. 0.5VA
|
|
CT
|
Max. 1.0VA
|
|
Input contact 3EA
|
Digital Input : AC/DC 110V
|
|
Output
Contact
|
2EA for Power
|
AC 250V 16A / DC 30V 16A, Resistive Load
4000VA, 480W
|
|
8EA for Alarm (7a 1c)
|
AC 250V 5A / DC 30V 5A, Resistive Load
1250VA, 150W
|
|
Insulation resistance
|
Over DC 500V 100㏁
|
|
Insulation voltage
|
AC 2kV (1kV) / for 1 min
|
|
Impulse voltage
|
AC 5kV (3kV) Over 1.2 × 50㎲
|
|
Overload withstand
|
Current circuit
|
2 In for 3 hours
20 In for 2 seconds
|
|
Voltage circuit
|
1.15 Vn for 3 hours
|
|
Fast transient disturbance
|
Power Input 4kV
Other Input 2kV (Analog input 1kV)
|
|
ESD (Electrostatic Discharge)
|
Air 8kV
Contact 6kV
|
|
Operation temperature
|
-10℃ ~ 55℃
|
|
Storage temperature
|
-25℃ ~ 70℃
|
|
Humidity
|
Average 30% ~ 80%
|
|
Altitude
|
1000m and below
|
|
Others
|
Non-impact place
Non-air pollution place
|
|
Standard
|
IEC 60255, IEC 61000-4, KEMC 1120
|
|
Dimension (W×H×D)
|
437×210×165 mm
|
|
Weight
|
10.5kg
|
|