Type
|
Specification
|
|
Wirings
|
1P2W, 1P3W, 3P3W, 3P4W
|
|
Input
|
Frequency
|
50Hz/60Hz
|
|
Voltage
|
PT
|
10~230V
|
|
GPT
|
2.2~230V
|
|
Current
|
CT
|
0.05~6A
|
|
Control voltage
|
AC/DC 110V
|
|
Power consumption
|
Max. 30W
|
|
Burden
|
PT
|
Max. 1.0VA
|
|
CT
|
Max. 1.0VA
|
|
Input contact 10EA
|
Digital Input : AC/DC 110V
|
|
Output
|
2EA for power
|
AC230V 16A / DC30V 16A, Resistive load
3680VA, 480W
|
AC230V 8A / DC30V 8A, Inductive load(cosØ=0.4, L/R=7ms)
1840VA, 240W |
|
8EA for alarm
|
AC230V 12A / DC25V 12A, Resistive load
2760VA, 300W
|
|
AC230V 6A / DC25V 6A, Inductive load(cosØ=0.4, L/R=7ms)
1880VA, 150W
|
|
Insulation resistance
|
Over DC 500V 100㏁
|
|
Insulation voltage
|
AC 2kV (1kV) / for 1 min
|
|
Impulse voltage
|
AC 5kV (3kV) Over 1.2 × 50㎲
|
|
Overload Withstand
|
Current circuit
|
2 In for 3 hours
20 In for 2 seconds
|
|
Voltage circuit
|
1.15 Vn for 3 hours
|
|
Fast transient disturbance
|
Power Input 4kV
Other Input 2kV (Analog input 1kV)
|
|
ESD (Electrostatic discharge)
|
Air 8kV
Contact 6kV
|
|
Operation temperature
|
-10℃ ~ 55℃
|
|
Storage temperature
|
-25℃ ~ 70℃
|
|
Humidity
|
30% ~ 80%
|
|
Altitude
|
1000m and below
|
|
Others
|
Non-impact place
Non-air pollution place
|
|
Standard
|
IEC 60255, IEC 61326, IEC 61000-4, KEMC 1110
|
|
Communication
|
MODBUS/RS-485, I-NET
|
|
Dimension (W×H×D)
|
190×255×116 (mm)
|
|
Weight
|
3.6 kg
|
|